Cost

Home

Furnace Maintenance & Repair

Dec 2015

Customer called because furnace was not coming on. After further diagnosis of furnace found gas valve not opening. Circuit board is supposed to send 24 v to the gas valve for it to open. The gas valve was getting 24 v but not opening. Ordered new valve and installed it. After install made sure part was working and heating sequence was working properly .

$320

San Antonio, TX

HVAC Repair

Sep 2015

Water was leaking into kitchen area from ceiling. After further inspection found water leaking from ducts that come from roof top units. Proceeded to check the drains for roof top units and found all drains for roof top units not clogged due to sludge build. All drains were tied in together due to the clogged drains water was not able to drain and draining inside the building. I blew out all drains to correct issue. Drains were now unclogged and working properly.

$255

Sugar Land, TX

Rooftop AC Installation & Repair

Aug 2015

Roof top unit was not cooling, after further inspection found unit low on refrigerant. Found leak on unit and proceeded to solder leak. After fixing leak rechecked for anymore leaks and found none. Began to pull vacuum on unit and charge with correct amount of refrigerant. After unit was fixed check for proper operation unit is working properly.

$450

Apple Valley, MN

HVAC Repair

Jun 2015

Evaporator froze in walk in freezer for Chick-Fil-A restaurant due to bad evaporator motor. Motor went out due to broken motor mount. Washed evaporator of all ice and replaced motor and motor mount. After install let freezer get down to temperature and checked for proper operation

$611

Sugar Land, TX

HVAC Repair

Jul 2015

Customer requested summer p/m on a/c units. Checked units electrical components, refrigerant levels, and motor amp draws. Found both condensor coils dirty washed coils and also found one unit lo on refrigerant. Units were now at peak performance.

$320

Marietta, GA

HVAC Repair

Jul 2015

Found grounded compressor and bad condensor fan motor for walk in cooler at Chick-Fil-A restaurant due to transformer at main power line burning out. Compressor and motors were not getting correct amount of voltage causing motors to go out. Replaced compressor and condensor fan motor. After install checked for proper unit operation cooler got down to temperature 40 degrees Fahrenheit.

$2k